Main applications
- Residential
- MDU (Multi Dwelling Units – apartments, condominiums, hotels, etc.)
- Light commercial (small office buildings, small retail/restaurant/gas station, etc.)
- Agricultural (farms, barns, silos, etc.)
- Government/municipal
- University/college
Simplified internal schematics
Device electrical interfaces
Inputs
- 4 line inputs on screw terminals: 3Â LÂ and 1Â N
- 4 current transformer inputs: 3 for L current measurements and 1 for N current measurement
Ethernet port
- 1 RJ45 connector
⚠CAUTION! Plug in or unplug the LAN cable only when the Device is powered off! The LAN cable connector must not be metallic in the parts touched by the user to plug in or unplug the cable.
Add-on interface
- Shelly proprietary serial interface
⚠CAUTION! High voltage on the add-on interface when the Device is powered!
Connectivity
- Wi-Fi
- Ethernet
- Bluetooth
Each connectivity option can be enabled or disabled by the user.
Safety features
- Internal temperature sensing and reporting
Supported load types
- Resistive (incandescent bulbs, heating devices)
- Capacitive (LED light drivers, capacitor banks, electronic equipment, motor start capacitors)
- Inductive (transformers, fans, refrigerators, air-conditioners)
User interface
Inputs
- One tactile dome button
- Press briefly to toggle the state of the relay in the attached Shelly Pro 3EM Switch Add-on.
- Press and hold for 5 sec to activate Device AP.
- Press and hold for 10 sec to factory reset.
Outputs
- LED indication
- Power: Red light if the power supply is connected.
- Wi-Fi (varies):
- Blue light if in AP mode.
- Red light if in STA mode, and not connected to a Wi-Fi network.
- Yellow light if in STA mode, and connected to a Wi-Fi network. Not connected to Shelly Cloud or Shelly Cloud disabled.
- Green light if in STA mode, and connected to a Wi-Fi network and the Shelly Cloud.
- The LED will be flashing Red/Blue if OTA update is in progress.
- LAN: Green light if LAN is connected.
- Count: Red light will be flashing when the Device is measuring energy according to settings with frequency dependent on the energy flowing through the measured circuit.
Specifications
| Type | Value |
| Physical | |
| Size (HxWxD): | 94x19x69 ±0.5 mm / 3.70×0.75×2.71 ±0.02 in |
| Weight: | 62 ±1 g / 2.19 ±0.05 oz |
| Mounting: | DIN rail |
| Screw terminals max torque: | 0.4 Nm / 4.43 lbin |
| Conductor cross section: | 0.5 to 2.5 mm² / 20 to 14 AWG (solid, stranded, and bootlace lugs) |
| Conductor stripped length: | 6 to 7 mm / 0.24 to 0.28 in |
| Shell material: | Plastic |
| Color: | White |
| Environmental | |
| Ambient temperature: | -20 °C to 40 °C / -5 °F to 105 °F |
| Humidity: | 30 % to 70 % RH |
| Max. altitude: | 2000 m / 6562 ft |
| Electrical | |
| Power supply voltage AC: | 100 – 260 V, 50/60 Hz |
| Power supply voltage DC: | N/A |
| Power consumption: | < 3 W |
| External protection: | Tripping characteristic B or C, 16A max. rated current, min. 6 kA interrupting rating, energy limiting class 3 |
| Sensors, meters | |
| Internal-temperature sensor: | Yes |
| Voltmeters (RMS for each phase): | 100 – 260 V |
| Voltmeters accuracy: | ±1 % |
| Ammeters (RMS via CT for each phase and the Neutral): | 0 – 120 A |
| Compatible CT | CT 120A |
| Ammeters accuracy: | ±1 % (2 – 120 A), ±2 % (1 – 2 A), ±5 % (0 – 1 A) |
| Power and energy meters: |
|
| Channel-to-channel calibration minimum load | 500 W per channel |
| No load threshold: | 30 VA per channel |
| Measurement data storage: | At least 60 days of 1 min data resolution |
| Data export: |
|
| Radio | |
| RF band: | 2400 – 2495 MHz |
| Max. RF power: | <20 dBm |
| Wi-Fi protocol: | 802.11 b/g/n |
| Wi-Fi Range: | Up to 30 m / 100 ft indoors and 50 m / 160 ft outdoors (Depends on local conditions) |
| Bluetooth Protocol: | 4.2 |
| Bluetooth Range: | Up to 10 m / 33 ft indoors and 30 m / 100 ft outdoors (Depends on local conditions) |
| MCU | |
| CPU: | ESP32-D0WDQ6 |
| Flash: | 16 MB |
| Firmware capabilities | |
| Webhooks (URL actions): | 20 with 5 URLs per hook |
| Scripting: | Yes |
| MQTT: | Yes |
| CoAP: | No |
Basic wiring diagrams
Legend
| Terminals | Wires | ||
| A | Phase A input | LA | Phase A live (110-240 V) wire |
| B | Phase B input | LB | Phase B live (110-240 V) wire |
| C | Phase C and power supply input | LC | Phase C live (110-240 V) wire |
| N | Neutral terminal | L | Mono-phase live (110-240 V) wire |
| IA | Phase A current transformer input | N | Neutral wire |
| IB | Phase B current transformer input | Current transformers | |
| IC | Phase C current transformer input | CTA | Phase A current transformer |
| IN | Neutral current transformer input | CTB | Phase B current transformer |
| CTC | Phase C current transformer | ||
| CTN | Neutral current transformer (Optional. Not included) | ||






Reviews